TECHNICAL & PERFORMANCE DATA PERFORMANCE CURVE GRUNDFOS DRAINAGE & WASTEWATER 38 OPERATING CONDITIONS Liquid Temperature 0°C to +40°C Max. Particle Size 10 mm Max. Installation Depth Minimum Pumping Level pH value of pumped liquid 10 m Down to 3 mm (after removal of strainer) 4 to 9 PHYSICAL ATTRIBUTES TECHNICAL DATA Power Supply Voltage 220-240 Volt, 50 Hz Power Supply Cable 5 m/ 10 m with plug Enclosure Class Suitable for submerged installation (IP68) Approvals and Markings C-Tick Compliance Impeller Type Semi-open MINIMUM PIT DIMENSIONS UNILIFT CC 570 mm - Top Discharge 400 mm - Side Discharge A D E B C 500 mm Model UNILIFT CC 5 UNILIFT CC 7 UNILIFT CC 9 Motor Power P2 (kW) 0.24 0.38 0.78 Connections Outlet (Top) Outlet (Side) ¾“, 1” or 1 ¼” Male 1 ¼ “ Female ¾“, 1” or 1 ¼” Male 1 ¼ “ Female ¾“, 1” or 1 ¼” Male 1 ¼ “ Female A (h) 306 306 342 B (w1) 160 160 160 Dimensions (mm) C (w2) D (outlet 1) 238 270 238 270 238 308 E (outlet 2) 90 90 90 Weight (kg) 5 5 7