Section 2.2 Pump performance If the pressure gauges are placed at the same geodetic height, or if a differential pressure gauge is used for the measurement, it is not necessary to compensate for the difference in height (h2-h1). In connection with in-line pumps, where inlet and outlet are placed at the same level, the two ports often have the same diameter. For these types of pumps a simplified formula is used to determine the head: p1 p2 h1 h2 Fig.2.2.7.a: Inlinepump with same geodetic hight on inlet and outlet. h2 = h1 Differential pressure (∆p) The differential pressure is the pressure difference between the pressures measured at two points, e.g. the pressure drops across valves in a system. Differential pressure is measured in the same units as pressure. Dry cooler System pressure The system pressure is the static pressure, which is present at a point in the system, when the pumps are not running. System pressure is important to consider when you deal with a closed system. The system pressure in (m) Hsta in the lowest point must always be higher than the height of the system in order to ensure that the system is filled with liquid and can be vented properly. h Chiller Hsyst Hsyst > h Fig.2.2.8: The system pressure Hsta in a closed system has to be higher than the physical height of the installation 88